CHEMZOL 9330

Part No: RXSOL-43-4022-025

Scale and Corrosion Inhibitor for closed loop systems without presence of any heavy metals

CHEMZOL 9330 Corrosion Scale Inhibitor Cooling Water Treatment is a powerful corrosion and scale inhibitor specially formulated for closed-loop hot and cold water systems. This advanced phosphonate-based blend is nitrite-free, heavy metal-free, and environmentally responsible. CHEMZOL 9330 protects metallic components from corrosion while preventing scale buildup, thus enhancing system lifespan and energy efficiency.

CHEMZOL 9330 Corrosion Scale Inhibitor is essentially non-toxic, does not contain zinc, chromate, or other environmentally harmful heavy metals, and is ideal for industrial water treatment applications where safety, performance, and sustainability are priorities.

Application

Key areas of use

  • Closed-loop chilled water systems
  • Hot water heating loops
  • Industrial cooling systems
  • HVAC & refrigeration circuits
  • Geothermal and solar thermal loops
Dose

Recommended Dosage of CHEMZOL 9330 Corrosion Scale Inhibitor without Heavy Metals

System Type Dosage Range
Closed Loop Systems 100 – 300 ppm
High Scaling Potential 250 – 400 ppm
Circulating Cooling Systems 100 – 250 ppm
Technical specifications
Parameter Value
Appearance Clear, pale amber liquid
Odor Mild, characteristic
pH (as supplied) Acidic
Specific Gravity @ 25°C 1.12 – 1.18
Solubility 100% water soluble
Biodegradability >90% (readily biodegradable)
Supply location

Corrosion Scale Inhibitor for Open Closed Cooling systems ECO manufacturer supplier distributor in Mumbai, Kandla, Kolkata, Vizag, Chennai, India, Fujairah, Dubai UAE, Muscat Oman, Kenya Africa. Get the best quality of Corrosion Scale Inhibitor for Open Closed Cooling systems ECO at a competitive price from us. We have ready stock of Corrosion Scale Inhibitor for Open Closed Cooling systems ECO in India, UAE Gulf, Oman, Kenya Africa. Contact us for bulk as well as small orders.

Note
Key Features & Benefits
  • Dual action: corrosion and scale prevention
  • Phosphonate and polymer blend for superior threshold inhibition
  • Nitrite-free, heavy metal-free, environmentally safer
  • Compatible with copper, brass, steel, and mixed metallurgy systems
  • Reduces downtime and maintenance costs
  • Suitable for high and low temperature closed-loop systems
  • Corrosion Scale Inhibitor for Open Closed Cooling systems ECO is a very efficient dispersant for hardness-salts and metallic-oxides.
  • Corrosion Scale Inhibitor for Open Closed Cooling systems ECO is also a very efficient corrosion-inhibitor.
  • Corrosion Scale Inhibitor for Open Closed Cooling systems ECO contains sequestrants, anionic polymers and wetting-agents.
  • Corrosion Scale Inhibitor for Open Closed Cooling systems ECO has been developed to avoid or remove deposits composed of calcium carbonate, calcium sulphate, magnesium hydroxide, iron oxide, insoluble phosphates and silicates.
  • Corrosion Scale Inhibitor for Open Closed Cooling systems ECO may be applied in closed, open and once-through cooling-water systems, desalinisation plants, phosphoric acid plant and all other systems where above mentioned deposits will occur.

Safety Data (MSDS)

Product Name RXSOL-40-4022
Product Type CHEMZOL 9330

 Company Details:

RX MARINE INTERNATIONAL
105, A wing , BSEL , TECH PARK.
VASHI ,NEW BOMBAY 400703 INDIA 

Phone +91 22 65113333 / 5555 / 9999 / 27611360
Fax +91 22 2781 1318 :::AOH :0091 9821214367
Email mail@rxmarine.com

Proprietory blend of polyphosphonate polymers for controlling scale and corrosion. Contains no heavy metal active matter.

Physical / chemical hazards

Irritant

Environmental Hazards

Human health

hazards

8

Ingestion

Severely irritating to mouth and gastrointestinal tract. Wash out mouth with water then drink plenty of water. Do not induce vomiting. Consult doctor and show this datasheet

Inhalation

No known ill effects. Not applicable

Skin Contact

Irritation and redness of skin. Soreness on prolonged contact. Wash with soap and water. Remove contaminated clothing for washing. Consult doctor in accordance with symptoms

Eye contact

Severe irritation. Prolonged contact may cause damage. Immediately rinse eye with sterile water for 20 minutes. Seek medical advice

Notes  to Doctor: None

 

Flammability

Non-flammable

Extinguishing media: Water spray jet, extinguishing powder or foam, carbon dioxide
Unsuitable extinguishing media NONE
Hazardous decompositions Decomposition generates oxides of carbon (CO and CO2) and sulphur (SO2)
Protective equipment Protective clothing and self-contained breathing apparatus.

Personal precautions

Wear full protective equipment - gloves, eye/face protection and overalls. Ensure sufficient air supply.

Environmental precautions

Do not allow to enter water courses.

Methods of clean up

Small spillages can be flushed to drain with additional water. Large spillages should be contained. Dilute and neutralise to pH 6-10 with a convenient acid before discharge to drain.

Handling

Avoid direct contact with product. Before eating, drinking or smoking wash hands with soap and water

Storage

Store above 10 C. Do not allow to freeze. Ensure that the container is firmly secure when not in use

Shelf life >12 months
Suitable packaging Polyethylene, polypropylene and stainless steel containers.
Unsuitable packaging Metals and alloys.

Exposure limits: Substance

No materials present that are listed in EH40/2005.
Long term WEL (8 Hr): ........................ ppm ....................... mg/m3
Short term WEL (15 min): .................. ppm ....................... mg/m

Engineering measures

None

Respiratory protection Not applicable.
Skin, hand and body protection Overalls, boots and rubber gloves.
Eye protection Chemical goggles or face shield.

Form

Solution

Boiling point [C]

>100

Colour

Clear

Decomposition temp (C):

Decomposes on heating

Odour

Slight

Specific Gravity > 1
Molecular weight: Solubility Completely miscible
pH Acidic
Flash point (C):  

Stability

Stable under normal conditions May crystalise below 0 C

Thermal decomposition

Decomposition generates oxides of carbon (CO and CO2) and sulphur (SO2)

Conditions to avoid High temperatures and evaporation of water
Materials to avoid Soft metals (aluminium, zinc etc) and strong acids.
Hazardous reactions No known hazardous reactions.
Decomposition products Decomposition generates oxides of carbon (CO and CO2) and sulphur (SO2)

Acute toxicity:

 

Oral;

Irritant

Dermal

Irritant

Inhalation

Nil hazard

Eye

Irritant

Other data

 

Biodegradability Fully biodegradable and persis tence

 

Ecotoxic effects: The polymers will contribute to the BOD and COD of the receiving waters - no data available
Other data Short term harm to equatic environment through pH effects.

Methods of dispos al

Small quantities can be dis posed of via a foul drain. Larger quantities should be handled by a licensed contractor in accordance with Waste Disposal Regulations.

Packaging disposal  Return empty containers to the supplier for recycling or des troy by cutting up or by  incineration. Do not use for potable water

 UN No.: N/A
Proper shipping name : Nil hazard for transport

Mode Regulation Class Packing group Ems No.  Stowage  Code

 Road/Rail

European - ADR/RID N/A N/A      
 Sea IMO / IMDG          
 Air  ICAO / IATA          

Risk Phrases

 

 R36/38

Irritating to eyes and Skin

Safety phrases  
S26  In case of contact with eyes, rinse immediately with plenty of water and s eek medical advice
 S37/39 Wear suitable gloves and eye/face protectio
 S45  In case of accident or if you feel unwell, s eek medical advice immediately (show the label where possible

 

The above information is based on current knowledge of the product at the time of publication and is given in good faith. it is believed to be correct but does not purport to be all-inclusive and shall therefore be used only as a guide.

DISCLAIMER OF LIABILITY :The information in this SDS was obtained from sources which we believe are reliable. However, the information is provided without any warranty, express or implied, regarding its correctness. The conditions or methods of handling, storage, use or disposal of the product are beyond our control and may be beyond our knowledge. For this and other reasons, we do not assume responsibility and expressly disclaim liability for loss, damage or expense arising out of or in any way connected with the handling, storage, use or disposal of the product. This MSDS was prepared and is to be used only for this product. If the product is used as a component in another product, this MSDS information may not be applicable.